Honeywell IQ8Control C Installation Instruction page 67

Fire alarm control panel
Hide thumbs Also See for IQ8Control C:
Table of Contents

Advertisement

®
5.1.2.1
esserbus
Available loop alarm devices for directly connection to the esserbus
Part No.
Fire detector IQ8Quad
802383
802384
802385, 802385.SVxx
802386, 802386.SVxx
Alarm device IQ8Alarm
807205, 807206
807212, 807213, 807214,
807224
807322, 807332
807372, 807372.SVxx
Base sounder
806282
®
esserbus
PLus loop length
≤ 700 m
1000 m
1300 m
1600 m
2000 m
2500 m
3000 m
3500 m (max. loop length)
Example: The following alarm devices are connected to a loop:
8 Fire detector IQ8Quad (Part No. 802385) with load factor 3
9 alarm devices IQ8Alarm with load factor 3
Result:
The total load factor obtained in this example allows for a loop length of max.1600 m (refer table).
observe max. permitted loop length
check compatibility of loop devices
do not exceed the max. admissible total load factor of 96 (per loop)
observe max. number of alarm devices on the loop for each individual device type
max. total number of 127 loop devices per loop
1)
refer table chapter 5.1.3.
FB 798951.GB0 / 01.09
PLus alarm devices
Name
Visual
Audible
Visual + audible + speech
Audible + speech
Audible
Visual
sphere colour red or amber
white, blue or green
Audible + speech
Audible + visual
Audible + visual + speech
Audible
Total load factor
Fire Alarm Control Panel IQ8Control C/M
®
PLus analog loop.
Max. total load factor
96
78
66
54
48
42
36
30
= Load factor 24
= Load factor 27
______________
=
1)
Load factor (LF)
+
51
2
3
3
2
67