Honeywell IQ8Control C Installation Instruction page 110

Fire alarm control panel
Hide thumbs Also See for IQ8Control C:
Table of Contents

Advertisement

Fire Alarm Control Panel IQ8Control C/M
Checking the essernet
An additional check of the essernet
(from index "E" onwards).
Switching on the display on the fire alarm control panel:
Test
Press key
The displays are switched off using the key switch.
Display
Direction 12
Direction 34
Fault 12 [%]
Fault 34 [%]
Fault. Max 12 [%]
Fault. Max 34 [%]
Repeat telegram
Panel no.
The counters are reset when the FACP is restarted.
110
®
devices and connections
®
devices/connections can be carried out using the essernet
Test
Value
Meaning
(example)
1555
Number of telegrams received without error at terminals 1+2 of the
®
essernet
Automatic update of the values:
®
essernet
®
essernet
1551
Terminals 3+4 (see "Direction 12")
Percentage display of the faulty telegrams which are received at
0
terminals 1+2 of the essernet
values:
®
essernet
®
essernet
0
Terminals 3+4 (see "Fault 12")
6
Maximum percentage value of the faulty telegrams received at terminals
1+2 since the panel was last restarted. This function enables a
measurement over a longer period and is reset to "0" after every restart
of the FACP.
8
Terminals 3+4 (see "Fault. Max 12")
4
Number of repetition requests.
Repetition requests for telegrams are a sign that there are faults on a
module or on the transmission path.
10
Display of the micro module address which has been set on the
®
essernet
of the FACP.
F3
micro module.
micro module 62.5 kBd: every 45 seconds
micro module 500 kBd: every 10 seconds
®
micro module. Automatic update of the
micro module 62.5 kBd: every 45 seconds
micro module 500 kBd: every 10 seconds
module. This address must correspond to the customer data
®
micro modules
6
FB 798951.GB0 / 01.09