CHAPTER 5: SETTINGS
Y LV
SRC 1
Phase CT
M1
Ground CT
M1
Phase VT
M5
Aux VT
None
5.5.4 Breakers
SETTINGS SYSTEM SETUP BREAKERS BREAKER 1(2)
BREAKER 1
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-48: Example of use of sources
D HV
AUX
SRC 2
SRC 3
F1+F5
None
None
None
None
None
None
U1
BREAKER 1
FUNCTION: Disabled
BREAKER1 PUSH BUTTON
CONTROL: Disabled
BREAKER 1 NAME:
Bkr 1
BREAKER 1 MODE:
3-Pole
BREAKER 1 OPEN:
Off
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: up to six alphanumeric characters
Range: 3-Pole, 1-Pole
Range: FlexLogic operand
SYSTEM SETUP
5
5-117