CHAPTER 5: SETTINGS
3.
Modify the user access rights by enabling or disabling one or more of the check boxes.
The table outlines access rights.
Table 5-2: Access rights summary
Field
Description
Delete Entry
Deletes the user account when exiting the user management window
Actual Values
Allows the user to read actual values
Settings
Allows the user to read setting values
Commands
Allows the user to execute commands
Event Recorder
Allows the user to use the digital fault recorder
FlexLogic
Allows the user to read FlexLogic values
Update Info
Allows the user to write to any function to which they have read privileges. When any of the Settings, Event
Recorder, and FlexLogic check boxes are enabled by themselves, the user is granted read access. When
any of them are enabled in conjunction with the Update Info box, they are granted read and write access.
The user is not granted write access to functions that are not enabled, even if the Update Info field is
enabled.
Admin
When this check box is enabled, the user becomes an EnerVista UR Setup administrator and has all
administrative rights. Exercise caution when granting administrator rights.
4.
Click OK to save the changes.
5.3.1.4 CyberSentry security
The EnerVista software provides the means to configure and authenticate the D30 access using either a server or the
device. Access to functions depends on user role.