CONTROL ELEMENTS
The reset time of the thermal overload protection element is also time delayed using following formula:
where
τ
= thermal protection trip time constant
rst
T
= a minimum reset time setting
min
5
The thermal overload protection element estimates accumulated thermal energy E using the following equations
calculated each power cycle. When current is greater than the pickup level, I
thermal energy:
5-252
(
kI
B
------------------------ -
t
=
τ
×
ln
rst
rst
2
I
(
Figure 5-142: IEC 255-8 sample operate and reset curves
E
=
E
+
------------- -
n
n 1
t
2
)
+
T
min
2
kI
)
B
> k × I
, element starts increasing the
n
B
t Δ
op In
( )
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Eq. 5-23
Eq. 5-24