FLEXLOGIC
Operand type
RxGOOSE Boolean
Virtual Input
Virtual Output
The following table lists alphabetically the operands available for the relay.
Table 5-16: D30 FlexLogic operands
Operand type
CONTROL
PUSHBUTTONS
CYBERSENTRY
5
DIRECT DEVICES
DIRECT INPUT/
OUTPUT CHANNEL
MONITORING
ELEMENT:
Autoreclose
(per CT bank)
ELEMENT:
Auxiliary overvoltage
ELEMENT:
Auxiliary
undervoltage
5-134
State
Example of format
On
RxGOOSE Boolean 1 On
On
Virt Ip 1 On
On
Virt Op 1 On
Operand syntax
CONTROL PUSHBTN 1 ON
CONTROL PUSHBTN 2 ON
CONTROL PUSHBTN 3 ON
CONTROL PUSHBTN 4 ON
CONTROL PUSHBTN 5 ON
CONTROL PUSHBTN 6 ON
CONTROL PUSHBTN 7 ON
ROLE ADMIN ACT
ROLE SUPERVISOR ACT
ROLE ENGINEER ACT
ROLE OPERATOR ACT
ROLE OBSERVER ACT
ROLE EXTERNAL ACT
AUTHENTICATION FAIL
UNAUTH FW ATTEMPT
UNAUTH SETTING WRITE
RADIUS SRV UNAVAILABLE
ACCT SRV UNAVAILABLE
DIRECT DEVICE 1On
DIRECT DEVICE 16On
DIRECT DEVICE 1Off
DIRECT DEVICE 16Off
DIR IO CH1 CRC ALARM
DIR IO CH2 CRC ALARM
DIR IO CH1 UNRET ALM
DIR IO CH2 UNRET ALM
AR1 ENABLED
AR1 RIP
AR1 LO
AR1 BLK FROM MAN CLS
AR1 CLOSE
AR1 SHOT CNT=0
AR1 SHOT CNT=1
AR1 SHOT CNT=2
AR1 SHOT CNT=3
AR1 SHOT CNT=4
AR1 DISABLED
AUX OV1 PKP
AUX OV1 DPO
AUX OV1 OP
AUX OV2 to 3
AUX UV1 PKP
AUX UV1 DPO
AUX UV1 OP
AUX UV2 to 3
Characteristics
[Input Is '1' (= ON) if...]
The RxGOOSE Boolean is presently in the ON state
The virtual input is presently in the ON state
The virtual output is presently in the set state (that is,
evaluation of the equation that produces this virtual output
results in a "1")
Operand description
Control pushbutton 1 is being pressed
Control pushbutton 2 is being pressed
Control pushbutton 3 is being pressed
Control pushbutton 4 is being pressed
Control pushbutton 5 is being pressed
Control pushbutton 6 is being pressed
Control pushbutton 7 is being pressed
Administrator role is active and is set to true when that is the case
Supervisor role is active and is set to true when that is the case
Engineer role is active and is set to true when that is the case
Operator role is active and is set to true when that is the case
Observer role is active and is set to true when that is the case
External role is active and is set to true when that is the case
Operand set for Failed Authentication self-test and alarm
Operand set for firmware lock self-test and alarm
Operand set for settings lock self-test and alarm
Operand set for RADIUS servers unavailable self-test
Operand set for ACCOUNTING servers unavailable self-test
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
The rate of direct input messages received on channel 1 and failing the CRC
exceeded the user-specified level
The rate of direct input messages received on channel 2 and failing the CRC
exceeded the user-specified level
The rate of returned direct input/output messages on channel 1 exceeded
the user-specified level (ring configurations only)
The rate of returned direct input/output messages on channel 2 exceeded
the user-specified level (ring configurations only)
Autoreclose 1 is enabled
Autoreclose 1 is in progress
Autoreclose 1 is locked out
Autoreclose 1 is temporarily disabled
Autoreclose 1 close command is issued
Autoreclose 1 shot count is 0
Autoreclose 1 shot count is 1
Autoreclose 1 shot count is 2
Autoreclose 1 shot count is 3
Autoreclose 1 shot count is 4
Autoreclose 1 is disabled
Auxiliary overvoltage element has picked up
Auxiliary overvoltage element has dropped out
Auxiliary overvoltage element has operated
Same set of operands as shown for AUX OV1
Auxiliary undervoltage element has picked up
Auxiliary undervoltage element has dropped out
Auxiliary undervoltage element has operated
Same set of operands as shown for AUX UV1
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL