GE D30 Instruction Manual page 467

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

CHAPTER 9: THEORY OF OPERATION
Normally, in order to respond to the fault shown in the figure, a distance relay is applied at the relaying point X. The table
outlines the relay input signals at this location.
Table 9-10: Relay input signals at location X
Input
Primary
VA
100.4 kV ∠–7.32°
VB
97.23 kV ∠–53.4°
VC
181.8 kV ∠–150.0°
IA
1.288 kA ∠–27.6°
IB
1.288 kA ∠152.4°
IC
0
If installed at the location X, the relay uses the following input signals for its phase AB distance element:
V = V
= 77.402 kV ∠57.5° primary or 29.49 V ∠57.5° secondary
AB
I = I
– I
= 2.576 kA ∠–27.6° primary or 42.93 A ∠–27.6° secondary
A
B
And consequently it sees an apparent impedance of
Z
= V / I = 30.05 Ω ∠85° primary or 0.687 Ω ∠85° secondary
app
If applied at location H, the relay sees the following input signals:
Table 9-11: Relay input signals at location H
Input
Primary
7.584 kV ∠–5.59°
VA
6.269 kV ∠–120.1°
VB
7.751 kV ∠125.5°
VC
IA
16.976 kA ∠–27.6°
IB
33.952 kA ∠152.4°
IC
16.976 kA ∠–27.6°
The relay is set as follows:
= "Dy11"
XFMR VOL CONNECTION
= "Dy11"
XFMR CUR CONNECTION
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 9-5: Sample system configuration
150 MVA, 10%
13.8kV/315kV
delta
wye, 330 lag
H
X
VT = 13.8kV/120V
VT = 315kV/120V
CT = 8000:5
CT = 300:5
2.57Ω∠88.4°
Secondary
38.25 V ∠–7.32°
37.04 V ∠–53.4°
69.26 V ∠–150.0°
21.47 A ∠–27.6°
21.47 A ∠152.4°
0
Secondary
69.95 V ∠–5.59°
54.52 V ∠–120.1°
65.84 V ∠125.5°
10.61 A ∠–27.6°
21.22 A ∠152.4°
10.61 A ∠–27.6°
PHASE DISTANCE APPLIED TO POWER TRANSFORMERS
°
AB
Z = 30.11
Ω∠
85°
L
Ω∠
0.688
85°
837727A2.CDR
9
9-15

Advertisement

Table of Contents
loading

Table of Contents