PRODUCT SETUP
Table 5-5: Security alarm settings
Setting name
Failed
Authentications
Firmware Lock
Settings Lock
CyberSentry settings through the front panel
SETTINGS  PRODUCT SETUP  SECURITY
 SECURITY
5
— This setting is applicable for Device authentication only. This setting allows a user to log in with a specific role, as
LOGIN
outlined here. For the Supervisor role, enable the "Supervisor Role" setting.
Whenever a new role is logged in, the user is prompted to enter a password. Passwords must obey the requirements
specified earlier in the chapter in the Password Requirements section.The UR device supports five roles. Roles have their
corresponding passwords, except the Observer role, which does not require a password.
The roles are defined as follows:
Administrator — Complete read/write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
Engineer — Complete read/write access to all settings and commands except configuring Security settings and
firmware upgrades. This role does not allow concurrent access.
Operator — The Operator has read/write access to all settings under the Commands menu/section. This role does not
exist offline.
Supervisor — This is only an approving role. This role's authentication commits setting changes submitted by
Administrator or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not
approve changes after the fact. Only a Supervisor can set the Settings Lock and Firmware Lock in the Security
settings. This role also has the ability to forcefully log off any other role and clear the security event log. This role can
also be disabled, but only through a Supervisor authentication. When this role is disabled its permissions are assigned
to the Administrator role.
5-20
Description / Details
A threshold number indicating when an alarm
is set off to indicate too many failed
authentication attempts
A value indicating if the device can receive a
firmware upgrade. If Enabled and a firmware
upgrade attempt is made, the device alarm
activates. If Disabled, the device alarm does not
activate. On each firmware upgrade this setting
goes back to the default.
A value indicating if the device can accept any
settings changes. If Enabled and a settings
change attempt is made, the device alarm
activates. If Disabled, the device alarm does not
activate.
LOGIN:
None
 CHANGE LOCAL
 PASSWORDS
 SESSION
 SETTINGS
 RESTORE DEFAULTS
 SUPERVISORY
SYSLOG IP ADDRESS:
0.0.0.0
SYSLOG PORT NUMBER:
514
Min
Max
Default
0
99
3
(disabled)
Disabled
Enabled Enabled
Disabled
Enabled Enabled
Range: Administrator, Engineer, Supervisor,
Operator, Factory (for factory use only), None
See page 5-21
See page 5-21
See page 5-21
See page 5-22
Range: 0.0.0.0, 255.255.255.255
Range: 1 to 65535
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Units
Minimum
permissions
-
Administrator
-
Administrator
-
Supervisor
(Administrator if
Supervisor has
been disabled)