Breakers - GE D30 series Instruction Manual

Line distance protection system. ur series
Hide thumbs Also See for D30 series:
Table of Contents

Advertisement

5 SETTINGS

PATH: SETTINGS
SYSTEM SETUP
 BREAKER 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin


BREAKERS

BREAKER 1(2)
BREAKER 1
FUNCTION: Disabled
BREAKER1 PUSH BUTTON
CONTROL: Disabled
BREAKER 1 NAME:
Bkr 1
BREAKER 1 MODE:
3-Pole
BREAKER 1 OPEN:
Off
BREAKER 1 BLK OPEN:
Off
BREAKER 1 CLOSE:
Off
BREAKER 1 BLK CLOSE:
Off
BREAKER 1 A/3P CLSD:
Off
BREAKER 1 A/3P OPND:
Off
BREAKER 1 B CLOSED:
Off
BREAKER 1 B OPENED:
Off
BREAKER 1 C CLOSED:
Off
BREAKER 1 C OPENED:
Off
BREAKER 1 Toperate:
0.070 s
BREAKER 1 EXT ALARM:
Off
BREAKER 1 ALARM
DELAY:
0.000 s
MANUAL CLOSE RECAL1
TIME:
0.000 s
BREAKER 1 OUT OF SV:
Off
BREAKER 1 EVENTS:
Disabled
D30 Line Distance Protection System
5.4 SYSTEM SETUP
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: up to 6 alphanumeric characters
Range: 3-Pole, 1-Pole
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: Disabled, Enabled
5.4.4 BREAKERS
5
5-83