GE D30 Instruction Manual page 336

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

GROUPED ELEMENTS
5.7.9.2 Ground time overcurrent (ANSI 51G, IEC PTOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  GROUND CURRENT  GROUND TOC1(2)
 GROUND TOC1
5
This element can provide a required time-delay operating characteristic versus the applied current or be used as a simple
definite time element. The ground current input value is the quantity measured by the ground input CT and is the
fundamental phasor or RMS magnitude. Two methods of resetting operation are available: "Timed" and "Instantaneous"
(see the Inverse TOC Curve Characteristics section for details). When the element is blocked, the time accumulator resets
according to the reset characteristic. For example, if the element reset characteristic is set to "Instantaneous" and the
element is blocked, the time accumulator clears immediately.
GROUND TOC1 FUNCTION
GROUND TOC1 SIGNAL SOURCE
GROUND TOC1 INPUT
selected as fundamental phasor magnitudes or total waveform RMS magnitudes as required by the application.
GROUND TOC1 PICKUP
GROUND TOC1 CURVE
GROUND TOC1 TD MULTIPLIER
Programming this value to zero results in an instantaneous response to all current levels above pickup.
GROUND TOC1 RESET
relays, which set the energy capacity directly to zero when the current falls below the reset threshold. The "Timed" reset
method can be used where the relay must coordinate with electromechanical relays.
GROUND TOC1 BLOCK
element.
GROUND TOC1 EVENTS
of events recorder.
These elements measure the current that is connected to the ground channel of a CT/VT module. The
conversion range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
5-204
GROUND TOC1
FUNCTION: Disabled
GROUND TOC1 SIGNAL
SOURCE: SRC 1
GROUND TOC1
INPUT: Phasor
GROUND TOC1
PICKUP: 1.000 pu
GROUND TOC1
CURVE: IEEE Mod Inv
GROUND TOC1
TD MULTIPLIER: 1.00
GROUND TOC1
RESET: Instantaneous
GROUND TOC1 BLOCK:
Off
GROUND TOC1
TARGET: Self-reset
GROUND TOC1
EVENTS: Disabled
— This setting enables and disables the ground time overcurrent protection element.
— This setting selects the signal source for the ground time overcurrent protection element.
— This setting selects how ground current input quantities are interpreted by the D30. Inputs can be
— This setting specifies the ground time overcurrent pickup level in per-unit values.
— This setting selects the inverse time overcurrent curve style.
— This setting specifies a multiple of the base curve shape specified by the
— The "Instantaneous" reset method is intended for applications with other relays, such as most static
— Assertion of the operand assigned to this setting blocks operation of the ground time overcurrent
— This setting enables and disables the logging of ground time overcurrent events in the sequence
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: Phasor, RMS
Range: 0.000 to 30.000 pu in steps of 0.001
Range: see the Overcurrent Curve Types table
Range: 0.00 to 600.00 in steps of 0.01
Range: Instantaneous, Timed
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
setting.
CURVE

Advertisement

Table of Contents
loading

Table of Contents