User-Programmable Leds - GE D30 Instruction Manual

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

PRODUCT SETUP
the type and number of CT/VT hardware modules installed, and
the type and number of analog input hardware modules installed
A list of all possible analog metering actual value parameters is presented in Appendix A: FlexAnalog Parameters. The
parameter index number shown in any of the tables is used to expedite the selection of the parameter on the relay display.
It can be time-consuming to scan through the list of parameters via the relay keypad and display — entering this number
via the relay keypad causes the corresponding parameter to display.
All eight CT/VT module channels are stored in the oscillography file. The CT/VT module channels are named as follows:
<slot_letter><terminal_number>—<I or V><phase A, B, or C, or 4th input>
The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB
designates the IB signal on terminal 2 of the CT/VT module in slot F.
If there are no CT/VT modules and analog input modules, no analog traces appear in the file; only the digital traces appear.

5.3.9 User-programmable LEDs

5.3.9.1 Menu
SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS
 USER-PROGRAMMABLE
 LEDS
5
The 48 amber LEDs on relay panels 2 and 3 can be customized to illuminate when a selected FlexLogic operand is in the
logic 1 state. The trip and alarm LEDs on panel 1 can also be customized in a similar manner. To ensure correct
functionality of all LEDs, an LED test feature is also provided.
5.3.9.2 LED test
SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS  LED TEST
 LED TEST
When enabled, the LED test can be initiated from any digital input or user-programmable condition, such as a user-
programmable pushbutton. The control operand is configured under the
LEDs, including the LEDs of the optional user-programmable pushbuttons.
The test consists of the following three stages:
1.
All 62 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is "burned." This stage lasts as
long as the control input is on, up to a maximum of 1 minute. After 1 minute, the test ends.
2.
All the LEDs are turned off, and then one LED at a time turns on for 1 second, then back off. The test routine starts at
the top left panel, moving from the top to bottom of each LED column. This test checks for hardware failures that lead
to more than one LED being turned on from a single logic point. This stage can be interrupted at any time.
3.
All the LEDs are turned on. One LED at a time turns off for 1 second, then back on. The test routine starts at the top left
panel moving from top to bottom of each column of the LEDs. This test checks for hardware failures that lead to more
than one LED being turned off from a single logic point. This stage can be interrupted at any time.
5-90
 LED TEST
 TRIP & ALARM LEDS
 USER-PROGRAMMABLE
 LED 1
 USER-PROGRAMMABLE
 LED 48
LED TEST FUNCTION:
Disabled
LED TEST CONTROL:
Off
See below
See page 5-92
See page 5-92
Range: Disabled, Enabled
Range: FlexLogic operand
setting. The test covers all
LED TEST CONTROL
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS