GE D30 Instruction Manual page 202

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

PRODUCT SETUP
Commands
The UR implements a number of clear records commands as detailed in the Commands and Targets chapter of this
manual. Several of these commands also can be issued via IEC 61850. The settings related to these IEC 61850 commands
are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Commands to access the settings that configure
the IEC 61850 protocol interface for record clear commands.
5
FltRptRFLO1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo"
here is select-before-operate. Enhanced security means that the D30 reports to the client the breaker 1 position at the
end of the command sequence.
LLN0.EvtRcdClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR EVENT RECORDS.
LPHD1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR ALL RELAY RECORDS.
OscRDRE1.RcdTrg.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command FORCE TRIGGER.
5-70
Figure 5-26: Commands panel
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS

Advertisement

Table of Contents
loading

Table of Contents