CHAPTER 6: ACTUAL VALUES
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, 'Virt Op 1' refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.
6.2.8 Autoreclose
ACTUAL VALUES STATUS AUTORECLOSE AUTORECLOSE 1
AUTORECLOSE 1
This menu displays the reclosure shot count.
6.2.9 RxGOOSE status
ACTUAL VALUES STATUS RxGOOSE STATUS
RxGOOSE STATUS
The D30 is provided with optional IEC 61850 capability. This feature is specified as a software option at
the time of ordering. See the Order Codes section of chapter 2 for details.
The
actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
All RxGOOSE Online
Input.
6.2.10 RxGOOSE statistics
ACTUAL VALUES STATUS RxGOOSE STATISTICS RxGOOSE 1(16)
RxGOOSE 1
The D30 is provided with optional IEC 61850 capability. This feature is specified as a software option at
the time of ordering. See the Order Codes section of chapter 2 for details.
— State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
— Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
AUTORECLOSE 1
SHOT COUNT:
0
All RxGOOSE Online:
Yes
RxGOOSE 1:
Off
RxGOOSE 16:
Off
RxGOOSE 1
stNum:
0
RxGOOSE 1
sqNum:
0
Range: 0, 1, 2, 3, 4
Range: Yes, No
Range: On, Off
Range: On, Off
STATUS
6