CHAPTER 5: SETTINGS
5.7.7.4 Phase instantaneous overcurrent (ANSI 50P, IEC PIOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT  PHASE IOC 1(4)
 PHASE IOC 1
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-103: Phase time overcurrent 1 logic
PHASE IOC1
FUNCTION: Disabled
PHASE IOC1 SIGNAL
SOURCE: SRC 1
PHASE IOC1
PICKUP: 1.000 pu
PHASE IOC1 PICKUP
DELAY: 0.00 s
PHASE IOC1 RESET
DELAY: 0.00 s
PHASE IOC1 BLOCK A:
Off
PHASE IOC1 BLOCK C:
Off
PHASE IOC1
TARGET: Self-reset
PHASE IOC1
EVENTS: Disabled
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 0.000 to 30.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled