PRODUCT SETUP
When the "Server" Authentication Type is selected, the D30 uses the RADIUS server and not its local authentication
database to authenticate the user.
When the "Device" button is selected, the D30 uses its local authentication database and not the RADIUS server to
authenticate the user. In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Operator, Observer), as login
accounts and the associated passwords are stored on the D30 device. In this case, access is not user-attributable. In cases
where user-attributable access is required, especially for auditable processes for compliance reasons, use server
authentication (RADIUS) only.
No password or security information is displayed in plain text by the EnerVista software or the UR device, nor are they ever
transmitted without cryptographic protection.
Only (TCP/UDP) ports and services that are needed for device configuration and for customer enabled features
5
are open. All the other ports are closed. For example, Modbus is on by default, so its TCP port 502, is open. But if
NOTE
Modbus is disabled, port 502 is closed. This function has been tested and no unused ports have been found
open.
When CyberSentry is enabled, Modbus communications over Ethernet is encrypted, which is not always tolerated by
SCADA systems. The UR has a bypass access feature for such situations, which allows unencrypted Modbus over Ethernet.
This "Bypass Access" setting is available on the
other protocols (DNP, 101, 103, 104, EGD) are not encrypted, and they are good communications options for SCADA
systems when CyberSentry is enabled.
CyberSentry settings through EnerVista
CyberSentry security settings are configured under Device > Settings > Product Setup > Security.
5-16
Figure 5-2: Login screen for CyberSentry
SETTINGS  PRODUCT SETUP  SECURITY  SUPERVISORY
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
screen. Note that