GE D30 Instruction Manual page 186

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

PRODUCT SETUP
RxGOOSE1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
If the value entered is non-zero, the confRev field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the entered value is zero, RxGOOSE1 does not check the value
received in the confRev field.
If the publisher is a UR 7.3x series device, set this setting to match the value of the publisher's TxGOOSE ConfRev setting.
RxGOOSE1 Member 1
Range: End of List, BOOLEAN, Dbpos, FLOAT32, INT32, Quality, TimeStamp
Default: End of List
This setting specifies the type that the first member of incoming GOOSE messages must be for the message to be
accepted as a valid RxGOOSE1 message. There are similar settings for each of the members that the UR is able to
subscribe to in a given GOOSE message. The member before the first member setting set to "End of List" must be the last
member of the message for the message to be accepted as a valid RxGOOSE1 message.
If the publisher is a UR 7.3x series device, set these settings to match the basic type of the members of the publisher's
data set selected by the publisher's TxGOOSE datSet setting.
RxGOOSE inputs
The values received by RxGOOSE elements need to be converted to FlexLogic or FlexAnalog operands so that they can be
used by other UR elements. This conversion is done by RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements.
Each RxGOOSE Boolean can convert the value of a specified Boolean member received by a specified RxGOOSE to a
FlexLogic operand. Each RxGOOSE DPS can convert the value of a specified Dbpos (Double bit position) member to four
FlexLogic operands, one for each of the four possible Dbpos states. Each RxGOOSE Analog can convert the value of a
5
specified FLOAT32 member to a FlexAnalog operand. Each of these operands reverts to its default state when the
RxGOOSE connectivity is lost. INT32, Quality, and TimeStamp members cannot be converted to operands, and thus
although they can be accepted in GOOSE messages, they have no effect on the UR.
RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements are mapped to various data objects in
<iedName>Master/GGIO3. This is to allow reading of their values via MMS and to allow references to them in SCL files.
GGIO3 has no settings, nor is it visible via UR Setup software. See the UR Communications Guide for more information on
GGIO3.
RxGOOSE Boolean inputs
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Boolean Inputs
> RxGOOSE Boolean1 to access the settings for the first RxGOOSE Boolean. The settings and functionality for the others
are similar.
5-54
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS