GE D30 Instruction Manual page 452

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

PHASE DISTANCE THROUGH POWER TRANSFORMERS
The Zone 1 settings are:
PHS DIST Z1 REACH
: "85"
PHS DIST Z1 RCA
PHS DIST Z1 XMFR VOL CONNECTION
PHS DIST Z1 XMFR CUR CONNECTION
The Zone 3 settings are:
PHS DIST Z3 REACH
: "89"
PHS DIST Z3 RCA
PHS DIST Z3 XMFR VOL CONNECTION
PHS DIST Z3 XMFR CUR CONNECTION
8
8-10
Z
=
30
×
1
: "0.80"
: "None"
: "Dy1"
Z
=
(
0.127 90°
+
0.006 88°
3
: "2.60"
: "Yd11"
: "None"
13.8
1600
---------
×
---------- -
=
0.8011Ω 85°
315
2625
315
1600
---------
---------- -
)
×
×
=
2.601Ω 89.4°
13.8
2625
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 8: APPLICATION OF SETTINGS
Eq. 8-9
Eq. 8-10