CHAPTER 5: SETTINGS
SETTINGS
TRIP BUS 1 INPUT 1
= Off
TRIP BUS 1 INPUT 2
= Off
TRIP BUS 1 INPUT 16
= Off
SETTINGS
TRIP BUS 1
FUNCTION
= Enabled
TRIP BUS 1 BLOCK
= Off
SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
FLEXLOGIC OPERAND
RESET OP

5.8.3 Setting groups

SETTINGS  CONTROL ELEMENTS  SETTING GROUPS
 SETTING GROUPS
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the
settings menu. The active setting group can be indicated on the front display of the UR by configuring User-
ELEMENTS
Programmable LEDs to display the state of the
— When Enabled, allows setting groups other than group 1 (the default active group) to be
SETTING GROUPS FUNCTION
activated. The default setting group is forced active while the
Prevents the active setting group from changing when the selected FlexLogic operand is "On." This
SETTING GROUPS BLK —
can be useful in applications where it is undesirable to change the settings under certain conditions, such as during a
control sequence.
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-125: Trip bus logic
Non-volatile,
set-dominant
OR
AND
S
Latch
R
AND
OR
SETTING GROUPS
FUNCTION: Enabled
SETTING GROUPS BLK:
Off
GROUP 2 ACTIVATE ON:
Off
GROUP 6 ACTIVATE ON:
Off
GROUP 1 NAME:
GROUP 6 NAME:
SETTING GROUP
EVENTS: Disabled
SETTING GROUP ACT
SETTING GROUPS FUNCTION
SETTINGS
TRIP BUS 1 PICKUP
DELAY
TRIP BUS 1 RESET
DELAY
T
PKP
T
RST
Range: Disabled, Enabled
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: up to 16 alphanumeric characters
Range: up to 16 alphanumeric characters
Range: Disabled, Enabled
FlexLogic operands.
setting is Disabled.
CONTROL ELEMENTS
FLEXLOGIC OPERAND
TRIP BUS 1 OP
FLEXLOGIC OPERAND
TRIP BUS 1 PKP
842023A1.CDR
GROUPED
5-221