Breakers - GE C70 Instruction Manual

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

5.4 SYSTEM SETUP

PATH: SETTINGS
SYSTEM SETUP
 BREAKER 1
5
5-96


BREAKERS

BREAKER 1
FUNCTION: Disabled
BREAKER1 PUSH BUTTON
MESSAGE
CONTROL: Disabled
BREAKER 1 NAME:
MESSAGE
Bkr 1
BREAKER 1 MODE:
MESSAGE
3-Pole
BREAKER 1 OPEN:
MESSAGE
Off
BREAKER 1 BLK OPEN:
MESSAGE
Off
BREAKER 1 CLOSE:
MESSAGE
Off
BREAKER 1 BLK CLOSE:
MESSAGE
Off
BREAKER 1 A/3P CLSD:
MESSAGE
Off
BREAKER 1 A/3P OPND:
MESSAGE
Off
BREAKER 1 B CLOSED:
MESSAGE
Off
BREAKER 1 B OPENED:
MESSAGE
Off
BREAKER 1 C CLOSED:
MESSAGE
Off
BREAKER 1 C OPENED:
MESSAGE
Off
BREAKER 1 Toperate:
MESSAGE
0.070 s
BREAKER 1 EXT ALARM:
MESSAGE
Off
BREAKER 1 ALARM
MESSAGE
DELAY:
MANUAL CLOSE RECAL1
MESSAGE
TIME:
BREAKER 1 OUT OF SV:
MESSAGE
Off
BREAKER 1 EVENTS:
MESSAGE
Disabled
C70 Capacitor Bank Protection and Control System
BREAKER 1
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: up to 6 alphanumeric characters
Range: 3-Pole, 1-Pole
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
0.000 s
Range: FlexLogic operand
Range: Disabled, Enabled
5 SETTINGS
5.4.4 BREAKERS