5.7.11.3 Phase overvoltage (ANSI 59P, IEC PTOV)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS  PHASE OVERVOLTAGE1(3)
5
 PHASE
 OVERVOLTAGE1
There are three phase overvoltage elements available. A phase overvoltage element is used as an instantaneous element
with no intentional time delay or as a definite time element. The input voltage is the phase-to-phase voltage, either
measured directly from delta-connected VTs or as calculated from phase-to-ground (wye) connected VTs. The figure
shows specific voltages to be used for each phase.
5-214
Figure 5-118: Phase undervoltage1 logic
PHASE OV1
FUNCTION: Disabled
PHASE OV1 SIGNAL
SOURCE: SRC 1
PHASE OV1
PICKUP: 1.000 pu
PHASE OV1 PICKUP
DELAY: 1.00 s
PHASE OV1 RESET
DELAY: 1.00 s
PHASE OV1 BLOCK:
Off
PHASE OV1
TARGET: Self-reset
PHASE OV1
EVENTS: Disabled
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic Operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS