Upgrade Software - GE D30 Instruction Manual

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

CHAPTER 10: MAINTENANCE
5.
Set the device to "programmed" under Settings > Produce Setup > Installation.
6.
If you changed the Remote Setting Authorized, the Local Setting Authorized settings, or relay lock settings, return
them to their previous settings.
7.
To apply any previously saved settings, right-click the saved settings file in the Offline Window area and select Write
to Device.
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (that is,
default values, minimum/maximum values, data type, and item size) can change slightly from version to
NOTE
version of firmware. The addresses are rearranged when new features are added or existing features are
enhanced or modified. The EEPROM DATA ERROR message displayed after upgrading/downgrading the
firmware is a resettable, self-test message intended to inform users that the Modbus addresses have changed
with the upgraded firmware. This message does not signal any problems when appearing after firmware
upgrades.

10.4 Upgrade software

The latest EnerVista software and firmware can be downloaded from
http://www.gedigitalenergy.com/app/ViewFiles.aspx?prod=urfamily&type=7
After upgrading, check the version number under Help > About. If the new version does not display, try uninstalling the
software and reinstalling the new versions.
A message can display in the EnerVista software when accessing a UR device that the "relay has a firmware version that
does not match EnerVista UR Setup's version for the device." This means that the order codes for the UR device and in the
EnerVista software are inconsistent. In the example shown, the N60 v7.2 is really a v7.1 device. The device is still functional,
but the message displays each time the device is accessed. This can be fixed by making the order codes consistent.
Figure 10-3: Mismatch in order code between software and device
To make the order codes consistent:
1.
In EnerVista, click the Device Setup button. The window opens.
2.
Expand the entry for the UR device.
3.
Click the Read Order Code button. The order code and version of the device are populated to the software.