Configure Ethernet Communication - GE D30 Instruction Manual

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

CONFIGURE THE D30 FOR SOFTWARE ACCESS

3.7.2 Configure Ethernet communication

You connect the cable, define a site, then add the relay as a device at that site. The computer and UR device must be on
the same subnet.
1.
Connect the Ethernet network cable to the Ethernet port on the back of the device.
2.
On the computer, select the UR device from the EnerVista Launchpad to start EnerVista UR Setup.
3.
Click the Device Setup button to open the Device Setup window, then click the Add Site button to define a new site.
4.
Enter a site name in the "Site Name" field. If wanted, a short description of site can also be entered along with the
display order of devices defined for the site. In this example, we use "Location 2" as the site name. Click the OK button
when complete.
The new site appears in the upper-left list in the EnerVista UR Setup window.
5.
Click the Device Setup button then select the new site to re-open the Device Setup window.
3
6.
Click the Add Device button to define the new device.
7.
Enter a name in the "Device Name" field and a description (optional) of the site.
8.
Select "Ethernet" from the Interface drop-down list. This displays a number of interface parameters that must be
entered for proper Ethernet functionality.
9.
Enter the relay IP address specified in the front panel
 IP ADDRESS
10. Enter the relay slave address and Modbus port address values from the respective settings in the front panel
 PRODUCT SETUP  COMMUNICATIONS MODBUS PROTOCOL
11. Click the Read Order Code button to connect to the D30 device and upload the order code. If an communications
error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay
setting values.
12. Click OK when the relay order code has been received. The new device is added to the Site List window (or Online
window) located in the top left corner of the main EnerVista UR Setup window.
The Site Device has now been configured for Ethernet communications. Proceed to the Connect to the D30 section to
begin communications.
3-46
Figure 3-56: Configuring Ethernet communication
in the IP Address field.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  NETWORK
menu.