Buzzer Menu

The Buzzer menu allows users to select whether or not the built-in
audible alarm can be silenced by pressing a keypad button and which
events will activate the buzzer.
Press enter in the main Buzzer menu screen. The Buzzer
screen displays either Activate or Silence.
Use the arrow keys to scroll to the desired option and press
enter to select.
If Silence is selected, the buzzer can be deactivated (without affecting
the event) by pressing and holding any key on the unit for 5 seconds.
Select Activate to display available menu options:
Network:
If the unit is configured with the Modbus or BACnet
communication protocol, these options are replaced with
Network. No action can be taken from this option: it simply
informs you that the buzzer is controlled by the network
master device.
Disable:
Only available if the unit is configured to emulate a 201T
(previous generation of Honeywell Analytics gas detectors
for toxic and combustible gases).
When the E
device controls the relay and buzzer together; they cannot be
controlled separately.
E
Point Network Gas Monitor User Manual
3
* Menu *
Buzzer
Buzzer
Activate
Point is configured in 201T EMU mode, the controller
3