Consult the Programming Functions section of this manual for more
detailed information on transmitter blinking sequences and
programming.
Consult the 301C controller user manual for more detailed information
on using the controller's wireless network menu.
Problem
The transmitter
is not
connected to
301C controller
511398
5/07

Troubleshooting

Possible Cause
The transmitter has not
been powered up
Communication
problems:
The network can take up
to 2 hours to establish all
connections. Times are
affected by network
structure: Less
transmitters close to
301C, more time to
establish link); Distance
between furthest
transmitter and 301C
(more hops); Size of
network (the more
transmitters, the longer it
takes)
301W User Manual
Honeywell
Solution
Press pushbutton 1, then
pushbutton 2. If the transmitter is
on, LED 2 will blink once. If no
LEDs blink the unit is off and you
must power up the transmitter:
Press and hold pushbuttons 1 and
2. Count 5 blinks of both LEDs
and release.
Enable the 301C's Association
mode (wireless Network menu)
Make sur the unit is powered up
(see above)
Check that devices closer to 301C
are connected (is the unit closest
to it connected)
Activate a scan of all channels
(see Function 4 -Scan All
Channels ) and wait 30 minutes
Activate the 301C's Association
mode and wait 50 minutes.
Reset network parameters (see
Function 5 -Reset Network
Parameters to Zero) and wait 50
minutes
If the transmitter has still not
connected, contact Technical
Support.