IAQPoint2 Troubleshooting Guide
Version
Symptom
Temperature set-
point adjustment
range is restricted
to narrower than
50 - 95F (10 -
35C)
Features absent
from main display
screen
Gas reading seems
inaccurate.
Diagnostic
Cause
Tests
The monitor has
Check configura-
been configured
tion via Review\User
for narrower tem-
Config line 4.
perature limits
Navigate to Config-
ure \ Configure Dis-
The monitor is set
play \ Main Display
for simple display.
Dataset. Check the
settings
Navigate to Con-
The easy tem-
figure \ Configure
perature adjust
Display \ Easy Temp
screen is disabled
Adj.
by default
Check part number
Some software
to determine if
features are not
temperature and
available in basic
humidity sensors are
versions of the
fitted.
product.
Confirm that the gas
The monitor is
calibration port (as
sampling air from
shown in Figure 7) is
outside the duct.
plugged.
Solution
Enter level 2 pass-
word and navigate
to Configure \
Configure SetPoints
\ MaxTemp or
MinTemp.
Change the settings
under Configure \
Configure Display
\ Main Display
Dataset.
Enter level 2
password and
change the setting
under Configure \
Configure Display \
Easy Temp Adj.
Purchase a model
with all of the
desired features
such as relay and
temperature /
humidity sensor.
Plug gas calibration
port.