Once all the transmitters are mounted into position, there is a precise
order to follow when powering up the system.
1. Power up the 301C wireless controller and allow it to initialize
before powering up any of the transmitters.
2. Power up the transmitters one at a time, beginning with the
transmitter closest to the controller and working out to the farthest.
a.To power-up the transmitter press pushbuttons 1 and 2
simultaneously (located below the left and right LEDs,
respectively) and count 5 blinks of both LEDs, then release to
power up the transmitter. (LED 1 will blink while the transmitter
searches for a network.)
3. After all of the transmitters are powered up, you will need to wait
approximately 30 minutes to connect to the network.
Note: Depending on the number of transmitters and the distance
between transmitter and controller, it can take as long as 12
hours after initial startup to optimize the network.
The network should now be communicating and functional. If there are
any problems with the transmitters, the Troubleshooting section
provides some solutions to common problems.