7.4 Serial Com Menu

7.4.1 Overview

7.4.2
Menu
INTERFACE
Item
7.4.3
Menu
ADDRESS
Item
7.4.4
Menu
BAUD RATE
Item
7.4.5
AUTO LINE-FEED
Menu Item
7.4.6
TRANSMIT TEST
Menu Item
7.4.7
Menu
LEAVE MENU
Item
The Serial Com menu allows you to examine and change the settings for serial com-
munications as well as test the communications link.
Detailed instructions on operating the SC instrument in the SETUP Menu mode can
be found in "SETUP Menu mode" on page 23. A diagram of all menus is located in
"Setup Menu Reference" on page 157.
This menu item indicates which serial communications interface is installed in the
instrument: "
" or "
RS-232
RS-485
This allows you to examine and change the two-character address that the instrument
will respond to. The default address of "00" (ASCII codes decimal 30, decimal 30).
This allows you to examine and change the baud rate that the instrument uses for
serial communications. The default baud rate is 9600.
This allows you to examine the setting (on/off) of the auto line-feed function. When
set to "on", a line-feed character (ASCII code decimal 10) is transmitted just before the
carriage return (ASCII code decimal 13) that signifies the end of the instrument's
response.
If the instrument is connected to a dumb terminal or printer, inserting a line feed before
the carriage return will make each message sent by the instrument appear on a sepa-
rate line and thus be easier to read.
The default setting is "on".
When this menu item is selected, the instrument immediately transmits the message
"
" where "nn" is the two-character address of the instrument. Then the
ADDRESS nn TEST
message "
" is shown on the display. This helps detect wiring or other prob-
MESSAGE SENT
lems with serial communications from the instrument to the computer or PLC.
When the menu item is displayed, press [ENTER] to leave this menu. Press [EXIT] to
return to the RUN mode.
".