6. To set the device Span**, scroll to Set Span and change the
calibration value using this procedure:
a. Using the right arrow, move the cursor to xxx PPM (span value
field). Press Enter to select the field.
b. Use the up or down arrows to increase or decrease the value
(according to the calibration gas concentration).
c. Press Enter to confirm the value. The screen displays *waiting*
until the 301C receives a response, then the value is displayed
on screen.
d. Move the cursor back to Set Span and press Enter to validate
the calibration gas value.
e. The 301C requests a final confirmation. Press Enter to confirm
and start the calibration.
The device span is being calibrated. The screen will displays the
device's status as "In Calib" until the calibration is complete.
**When selecting Set Span, make sure that the device has been
exposed to the appropriate calibration gas, before and throughout the
calibration process.

Periodic Inspections and Calibration

Although the wireless transmitter is maintenance free, regular
inspections may still be necessary. The inspection frequency depends
on operating conditions, including operating under extreme
temperatures, exposure to contaminants or gas concentrations greater
than the lower explosive limits. A calibration inspection must be
included as part of a routine maintenance to ensure proper operation of
the gas detection unit.
511398
5/07
Cartridge Replacement and Calibration
Periodic Inspections and Calibration
Calib
007
Status:
Normal
Set Zero
Set Span
246
301W User Manual
Honeywell
301W