Property
Data Type
object_identifier
object_type
enumerated
event_state
enumerated
object_name
character string
out_of_service
boolean
polarity
enumerated
present_value
enumerated
reliability
enumerated
status_flags
in_alarm
boolean
fault
boolean
overridden
boolean
out_of_service
boolean
object_identifier
object_type
enumerated
event_state
enumerated
object_name
character string
out_of_service
boolean
polarity
enumerated
present_value
enumerated
reliability
enumerated
status_flags
in_alarm
boolean
fault
boolean
overridden
boolean
out_of_service
boolean
BACNet Objects and Properties
R
C
binary_input (6)
R
C
binary_input (3)
R
C
normal (0)
R
N
"IAQGOOD_BI"
R
R
FALSE
R
C
always Normal (0)
R
R
"if no faults and Conc <SP, True (1) else False (0)"
O
C
no_fault_detected (0)
R
C
always "false" (0)
R
C
always "false" (0)
R
C
always "false" (0)
R
C
reports true OOS state
R
C
binary_input (7)
R
C
binary_input (3)
R
C
normal (0)
R
N
"OVDTIMER_BI"
R
R
"false"
R
C
always Normal (0)
R
R
"if override timer running, "true" (1) else "false" (0)"
0
C
no_fault_detected (0)
R
C
always "false" (0)
R
C
always "false" (0)
R
C
always "false" (0)
R
R
reports true OOS state
Read Value
not writable
not writable
not writable
Any unique string 1-22 bytes
"true" or "false"
not writable
"only of out_of_service, "true" or "false""
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
Any unique string 1-22 bytes
"true" or "false"
not writable
"only of out_of_service, "true" or "false""
not writable
not writable
not writable
not writable
not writable