rH Calibration

The optional IAQPoint2 relative humidity sensor is pre-calibrated� However,
exposure to certain chemicals may cause the reading to shift over time� The
humidity reading can be recalibrated using the following procedure:
1� Determine the true rH level by use of a reference hygrometer�
2� Enter the level 2 password� By default, this is 2967�
3� Navigate to Calibrate\Calibrate rH�
4� Press [Target] to navigate to "Set Target rH"� Enter the relative humidity
reported by the reference instrument�
5� Press [Calibrate Offset]�
6� Verify that the message "in base cal" is displayed� This lasts about two
seconds�
7� Verify that the message "Calibration Done" is displayed�
8� Press [X]
9� Verify that the Current rH agrees with the reference hygrometer� Note that this
screen does not automatically update� If desired, an update can be forced by
exiting and re-entering this screen�
10� If desired, the factory calibration may be restored by pressing [Revert to
Factory Cal]
11� When satisfied, with the humidity reading, navigate to the main screen�