IAQPoint2™
Affected
Models
•
•
•
•
•
54
IAQPoint2 Troubleshooting Guide
Version
Symptom
The monitor does
not communicate
Network variable
seem to have stale
data
Data seems inac-
curate
Diagnostic
Cause
Tests
The wiring is not
compliant with the
rules for TP/FT-
10 networks as
described by the
Echelon Series
5000 Chip Data
Book chapter 5.
Configuration
properties set
wrong
LonMark Object
"offline"
LonMaker "Manage/
Test"
LonMark Object
"disabled"
Send "wink" com-
Incorrect device
mand.
addressed
Solution
Rewire for compli-
ance.
set "MaxSend-
Time", "MinSend-
Time", or "MinD-
elta" smaller.
Set "online"
Set "enabled"
Change node ad-
dressing.