Programming Functions

To access program functions, you must scroll through each of the
options in the menu until you reach the desired option. You cannot
navigate backward in the menu; if you have gone beyond the desired
option, you must continue scrolling and restart from the first option until
the desired option appears.
*01
CO2
Warm Up
+02
CO2
680
ppm
Password
* AA *
MainProg
Set ADR.
MainProg
Max Conc
MainProg
Out Min
MainProg
Out Max
MainProg
Alarm A
MainProg
Set 4mA
MainProg
Set 20mA
MainProg
Set Zero
MainProg
Set Span
MainProg
Reset
* Quit *
511105
2/07
MainProg
Set ADR.
M01
Set ADR.
Max Conc
2000 ppm
Out Min
SaveChg.
0
ppm
Out Max
SaveChg.
0
ppm
Alarm A
850
ppm
Set 4mA
SaveChg
Adj 4-20
Set 20mA
Adj 20mA
GoCalib?
Yes
CalibGas
800
ppm
Reset
Yes
Wait
Re-Init
Figure 6: Menu Structure
90DM4 User Manual
Honeywell
SaveChg.
Yes
Yes
Yes
MainProg
Alarm A
Yes
SaveChg
Yes
Cal.Zero
Cal.Zero
* Wait *
Complete
GoCalib?
Cal.Span
Yes
* Wait *
MainProg
Reset
Using the 90DM4
Programming Menus
Cal.Span
Complete
19