Honeywell IAQPoint2 User Manual page 74

Air quality monitor
Hide thumbs Also See for IAQPoint2:
Table of Contents

Advertisement

Available languages

Available languages

IAQPoint2™
Property
object_identifier
object_type
enumerated
event_state
enumerated
object_name
character string
out_of_service
boolean
polarity
enumerated
present_value
enumerated
priority_array
reliability
enumerated
relinquish_default
status_flags
in_alarm
boolean
fault
boolean
overridden
boolean
out_of_service
boolean
object_identifier
object_type
enumerated
event_state
enumerated
object_name
character string
out_of_service
boolean
polarity
enumerated
present_value
enumerated
priority_array
reliability
enumerated
relinquish_default
status_flags
in_alarm
boolean
fault
boolean
overridden
boolean
out_of_service
boolean
Notes:
1 -- 'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 -- 'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM�
68
BACNet Objects and Properties
Data Type
R
C
binary_output (8)
R
C
binary_output (4)
R
C
normal (0)
R
N
"RLY_DRV_BO"
R
C
FALSE
R
C
always Normal (0)
R
R
last value written
R
R
last value written
0
C
no_fault_detected (0)
R
C
"false" (0)
R
C
always "false" (0)
R
C
always "false" (0)
"if Relay configured to respond to fieldbus, "false" (0).
R
R
If relay configured to respond to gas or occupied timer or
relay absent, "true" (1)"
R
R
always "false" (0)
R
C
binary_output (9)
R
C
binary_output (4)
R
C
normal (0)
R
N
"OCC_DRV_BO"
R
C
FALSE
R
C
always Normal (0)
R
R
last value written
R
R
last value written
0
C
no_fault_detected (0)
R
C
"false" (0)
R
C
always "false" (0)
R
C
always "false" (0)
R
C
always "false" (0)
R
C
always "false" (0)
Read Value
not writable
not writable
not writable
Any unique string 1-22 bytes
not writable
not writable
"true" or "false"
"true" or "false"
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
Any unique string 1-22 bytes
not writable
not writable
"true" or "false"
"true" or "false"
not writable
not writable
not writable
not writable
not writable
not writable
Writable Values

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E3point

Table of Contents