Service and maintenance
8.4 Performing a firmware and project update
Upgrading with a CF card
1. Switch off the SIMOTION D410‑2 to be updated.
2. Insert the CF card into the SIMOTION D410‑2.
3. Switch on the SIMOTION D410‑2 again. The SIMOTION D410‑2 starts to process the
upgrade data.
The SF/BF LED flashes green (0.5 Hz) during the upgrade.
4. Monitor the green flashing of the SF/BF LED.
– As soon as the upgrade has been completed successfully, the SF LED goes out.
– If the upgrade was not successful, the SF/BF LED flickers red.
Downgrading
If the upgrade has not been successful (for example, the machine is not behaving as desired),
the upgrade can be undone as follows:
1. Switch off the SIMOTION D410‑2.
2. Set the service selector switch to the switch position B (service mode: downgrade).
Figure 8-9
3. Switch the D410‑2 on again.
The flickering green SF/BF LED indicates that restoration is requested.
4. Set the service selector switch back to position "0."
The system restores the data saved during the upgrade. The data from the upgrade will be
deleted.
The downgrade is indicated by a green flashing SF LED (0.5 Hz) and can take several minutes.
After successful restoration, the module starts up automatically. (SF/BF LED display will then
depend on the respective operating status of the device).
If the restore was not successful, the SF/BF LED will flicker red.
Note
If SIMOTION < V4.4, restoration will start when the module is switched on (step 3). For this,
the service selection switch must be rotated to position "0" immediately when the flashing code
is displayed (SF/BF LED flashes green with 0.5 Hz).
If the service selector switch is not reset or not reset in good time to "0," this results in fault
state "Service selector switch is still set to restore" (SF/BF LED flickers red).
In this case, switch the D410‑2 off, reset the service selector switch and switch the D410‑2 on
again. If the restoration was otherwise successful, the D410‑2 boots up with the restored
configuration.
284
An automatic start up with the upgraded configuration is then performed
(SF/BF LED display then depends on the associated operating state of the device).
Service selector switch, switch position for downgrading