Commissioning (software)
7.2 Performing an offline configuration
4. Select in the "Power Unit Supplementary Data" dialog the component added to the power
unit.
The selection of the component depends on the construction type.
– SIMOTION D410‑2 DP or D410‑2 DP/PN: The SIMOTION D410‑2 is snapped directly
– CUA31 or CUA32: The CUA3x is snapped directly onto the blocksize format Power
150
onto the blocksize format Power Module.
Module. The SIMOTION D410-2 is mounted separately on a mounting plate. The
SIMOTION D410‑2 is connected to the CUA3x using a DRIVE-CLiQ cable.
Figure 7-4
Selecting the mounting type
Note
If SIMOTION D410-2 is mounted separately (Power Module in blocksize format
connected to SIMOTION D410-2 via CUA31/32), use of the Safety Integrated Extended
functions via the on-board terminals (F-DI, F-DO) is not possible.
Commissioning and Hardware Installation Manual, 01/2015
SIMOTION D410-2