Establishing The Online Connection; Starting Automatic Configuration - Siemens SIMOTION D410-2DP/PN Installation Manual

Table of Contents

Advertisement

7.3.2

Establishing the online connection

Procedure when commissioning the drive for the first time
To perform an online configuration, you must establish an online connection to the
SIMOTION D410-2. In this case, no connection can yet be established to SINAMICS
Integrated. An appropriate message is output. Once the hardware configuration has been
loaded to the target device, an online connection to the SINAMICS Integrated is established
automatically. Proceed as follows:
1. Save and compile the project.
2. Establish an online connection.
3. Select the SIMOTION D410-2 device in the project navigator.
4. Use the "Download CPU / drive unit to target device" function to download the SIMOTION
D410-2 device to the target device. The connection to SINAMICS Integrated is activated
automatically.
You can now run automatic configuration on the SINAMICS Integrated. For details, see Section
Starting automatic configuration (Page 163).
Additional references
Further information about establishing an online connection to the programming device/PC
can be found in the following documentation:
SIMOTION SCOUT Configuration Manual
SIMOTION SCOUT Online Help
● In the FAQ for
SIMOTION Utilities & Applications is provided as part of the SIMOTION SCOUT scope of
delivery.
● FAQOnline connection to SIMOTION
en/22016709)
7.3.3

Starting automatic configuration

Requirement
You have established the online connection to SINAMICS Integrated.
SIMOTION D410-2
Commissioning and Hardware Installation Manual, 01/2015
SIMOTION Utilities & Applications
7.3 Performing an online configuration
(http://support.automation.siemens.com/WW/view/
Commissioning (software)
163

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotion d410-2 dp

Table of Contents