Procedure
1. In the "Interface Selection - D410" dialog box, select the entry "Ethernet PNxIE (X127)".
Figure 6-3
2. Select the interface parameter assignment that you would like to use to go online, and
confirm with "OK".
The dialog box is closed, the SIMOTION D410-2 is created in the project navigator and HW
Config is started automatically (if parameterized).
An Ethernet subnet with factory settings is created automatically. For factory settings, see
Section General information about communication via Ethernet (Page 134).
Result
The PG/PC is now connected to the SIMOTION D410-2 via Ethernet.
You can configure and parameterize your system.
Note
If you want to change the default settings for IP addresses and the transmission rate, you must
configure the Ethernet interfaces in HW Config and NetPro.
Make sure that the PG/PC and SIMOTION D410-2 are located in the same subnet and that
S7Online access has been activated (the PG/PC connection must appear yellow and bold in
NetPro).
SIMOTION D410-2
Commissioning and Hardware Installation Manual, 01/2015
6.2 Creating a project and configuring the communication
Selecting the Ethernet interface
Parameter assignment / addressing