5. The desired SINAMICS parameter is assigned to the I/O variable in the interconnection
dialog box.
Figure 7-31
6. Click "OK" to accept the assignment.
The following table shows the possible types of assignment:
Name of the assignment
BICO_IW.<parameter number>
BICO_QW.<parameter number>
BICO_ID.<parameter number>
BICO_QD.<parameter number>
Syntax of the assignment names
● A number of parameters (separated by periods) are specified for outputs (SINAMICS side
= received data) which can be interconnected with a number of BICO sinks
● If the transferred parameter is on another drive object (DO), the DO name precedes the
parameter. "#" is used as a separator between the DO name and the parameter.
● Individually transferred bits of a parameter appear in brackets [x]
SIMOTION D410-2
Commissioning and Hardware Installation Manual, 01/2015
Assigned drive parameters
Data type
WORD
WORD
DWORD
DWORD
Commissioning (software)
7.9 Symbolic assignment of I/O variables
Direction
Transferrable BICO parameters
Input
All CO parameters (BICO source)
Output
All CI parameters (BICO sink)
Input
All CO parameters (BICO source)
Output
All CI parameters (BICO sink)