Procedure
Proceed as follows to configure the PROFIBUS DP interface:
1. In the "Interface Selection - D410" dialog box, select the entry "PROFIBUS DP/MPI (X21)"
(in the case of the D410-2 DP, the following alternative is also available: PROFIBUS DP
(X24)).
Figure 6-2
2. Select the interface parameter assignment that you would like to use to go online, and
confirm with "OK".
The dialog box is closed, the SIMOTION D410-2 is created in the project navigator and HW
Config is started automatically (if parameterized).
A PROFIBUS subnet with factory settings (1.5 Mbit/s transmission rate) is created
automatically.
Result
The PG/PC is now connected to the SIMOTION D410-2 via PROFIBUS. You can configure
and parameterize your system.
Note
If you do not use the factory settings, you must configure the PROFIBUS interfaces in HW
Config.
Please make sure that the S7 online access has been activated (PG/PC connection must be
yellow and bold in NetPro).
SIMOTION D410-2
Commissioning and Hardware Installation Manual, 01/2015
6.2 Creating a project and configuring the communication
Selecting a PROFIBUS interface
Parameter assignment / addressing