Section IV Test Running

Failure occurred when test running, Please take reference of fault diagnosis in 6-1 to get rid
of the breakdown.
Inverter parameters have a strong adaptive ability, in general b11 = 1 calculation of electrical
parameters with the name plate, on this basis, a little manual adjustment can get you high-
performance vector control.
Only when the motor completely without the load can set b11=3motor rotation measurements.
Before the electrical parameter measurement finished, inverter can have the ourput voltage
any time, please ensure the safety.
Calculated using plate
test
running
power voltage inverter in the
rated input voltage range
power supply connect to RST of inverter, confirm
the correct grounded then supply power
Confirmed the inverter power matches to the
motor power ,reset the factory value of y00 =5
Select motor parameters, motor parameters set in accordance
with motor nameplate set of parameters, rated power, rated
current, rated voltage, the number of pole pairs, motor speed
Set the appropriate acceleration and deceleration time, the motor
maximum frequency F12, the fundamental frequency F15
Set the keyboard for a
given frequency of F01
Press the keyboard keys
are transferred to run FWD
forward running
direction of the motor
Y
Shut down after the motor
parameter tuning
b11=2
b11=1
Static frequency converter
measurement
Press FWD self-tuning start
(motor may be running safety)
The success of self-tuning
Y
Choose
F00Control mode
V/F
sensorless
vector
Control
control
16
Shut down power outages, swap
any two-phase motor line
N
b11=3
Measurement
converter operation
Set the appropriate F09/F10 acceleration
N
and deceleration parameters, F06/F07
torque control parameter
Sensor
vector
control