Section V Parameter Function Table
PID regulation fault.
P12
PID display range
A09 PID set value=PID set value(%)*P12
A10 PID feedback value=PID feedback value(%)*P12
If PID feedback 10V corresponding 4.0Mpa pressure, if need A09, A10 to display actual
value, only need to set P12 = 0.04.

5-2-9.Expanding Parameters:E00-E23(0x0600-0x0617)

Code
Description / LCD
E00
Load type
Details, see Appendix IV.
E01
Starting pressure deviation
E02
Starting delay time
Feedback pressure <given pressure –starting pressure deviation.
Continuously exceed E02 start delay time, the inverter will restart under in the standby mode
This parameter is used to prevent the inverter from frequent start-stop.
E03
Stop frequency
E04
Stop delay time
If the set frequency is less than or equal to E03 stop frequency, exceeding E04 stop delay
time, the inverter will change from running to the stop standby state.
The bigger E03 parameter setting, the easier to stop, E03 parameter is set to 0, indicating the
0.00~100.00
Setting Range
General
Pump
Fan
Injection machine
Textile machine
Hoist machine
Kowtow machine
belt conveyor
Variable frequency power
Multi-pumps constant
pressure water supply
Reserved
Reserved
Torque control
Voltage regulation power
Current regulation power
Extruding machine
0.0~100.0
0.0~3200.0
0~50.00
0.0~3200.0
114
-
1.00
Factory
Unit
Setting
0
1
2
3
4
5
6
7
-
0
8
9
10
11
12
13
14
15
%
10.0
s
5.0
Hz
5.00
s
5.0
Y
Change
Limited
N
Y
Y
N
Y