Powtran PI8600 F Series User Manual page 146

Frequency inverters
Table of Contents

Advertisement

Appendix I
I-3-2.
Definition for communication port B:
Communication
port B pins
Communication
port B signal
EIA/TIA T568A
EIA/TIA T568B
● 00H = 0 ID address is broadcast mailing address, 128 ~ 255 reserved. 00H = 0 ID address is
broadcast mailing address, 128 ~ 255 reserved.The number of inverter can be connected is no
more than 127.
● Though the length of communication cable can add up to 1300m, considering the stability, the
length limit within 800m
● All the control signal cable use the shield cable, and is linked to the signal terminal "SH" of
RS485.
● Data packet using CRC (vertical lengthy test) frame detection to ensure data reliability.
● Completely isolated RS485communication module to ensure reliable communications,support
hot-swappable, after modular access, you can enter the work.
● The system is tested in 6 kinds of baud rate: 0:1200, 1:2400, 2:4800, 3:9600, 4:19200, 5:38400
● However, if under deteriorating environmental conditions, lowering the baud rate can improve
the communication quality.
● Interval time of sending from frame to frame is more than 50 bytes.
I-4. Communication Protocol
Communication architecture is inverter as a slave, the computer as a host.
MODBUS protocol defines a simple protocol data unit (PDU) which has nothing to do with a
basic communication layer, Specific bus or network MODBUS protocol mapping can introduce
some additional domain from application data unit (ADU).
1
2
GND
+5V
485+
White
white
green
green
orange
White
White
orange
green
orange
3
4
5
485-
485+
white
blue
blue
white
blue
blue
144
6
7
8
485-
+5V
GND
white
orange
Brown
brown
white
green
brown
brown

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pi8600 g series