Motor Parameter:b00-B22(0X0800-0X0816) - Powtran PI8600 F Series User Manual

Frequency inverters
Table of Contents

Advertisement

Set the brake method when detect PG break.
0: NO PG break protection
1: Warning and keeping running
2: Warning and deceleration stop.
3: Warning and free stop.
C30
PG rotating direction
phase A
phase B
phase A is forward
Encoder rotating direction, refer to the motor forward direction
0: When motor forward, phase A leads, set C27= 0
1: When motor forward, phase B leads, set C27= 1
Note: above parameters are valid when with encoder(PG), need to layout PG card. If needed,
please contact our company.
C31
PG dropped inspection time
PG feedback signal is 0, exceed C31 set time, system reports PG dropped fault. Set speed to
0, or set C31 to 0, don‟t check PG dropped fault.

5-2-11.Motor Parameter:b00-b22(0x0800-0x0816)

Code
Description / LCD
b00
Motor 1 rated frequency
b01
Motor 1 rated current
b02
Motor 1 rated voltage
b03
Motor 1 pole-pairs
b04
Motor 1 rated speed
b00~b04 are the motor‟s nameplate parameters which touch the precision.Set the parameters
according to the motor‟s nameplate.
b00 ~ b04 motor nameplate in parameters, it is necessary to re-calculate motor parameters
by using
b11.Excellent vector control performance requires exact motor parameters. Exact parameters
are base on the correct setting of motor‟s rated parameters.
Section V Parameter Function Table
Warning and keeping
running
Warning and deceleration
stop
Warning and free stop.
When motor forward,
phase A leads
When motor forward,
phase B leads
phase A
phase B
phase B is forward
0.0~10.0
Setting Range
0.00~Max frequency
y09*(50%~100%)
100~1140
1~8
500~5000
125
1
2
3
0
-
0
1
s
1.0
Factory
Unit
Setting
Hz
50.00
A
V
-
2
rpm
1480
Y
N
Change
Limited
Y
Y
Y
Y
Y

Hide quick links: