Powtran PI8600 F Series User Manual page 16

Frequency inverters
Table of Contents

Advertisement

Section III Operation Keyboard
3-2-4.
F02 the main set mode of set frequency is set to 4, keyboard potentiometer setting !
1. Under monitoring status, Through potentiometer adjust the frequency, the resolution ratio
potentiometer is 0.05Hz.
2. Range of set frequency can be set with the following parameters:
Parameter item
F12 max. frequency
A45 keyboard potentiometer setting X1
A46 keyboard potentiometer setting X2
A47 keyboard potentiometer setting value
A48 keyboard potentiometer setting X1
correspond to Y1
A49 keyboard potentiometer setting X2
correspond to Y2
S00 setting frequency
Example:
F12=50.00Hz, A45=0%, A46=100%, A47 Shows the value of potentiometer settings 0%~100%,
Numerical size can be adjusted by potentiometer.
(1) When A48=0%, A49=+100%, S00 Set Fre.range 0.00Hz~50.00Hz.
(2) When A48=0%, A49=+50%, S00 Set Fre.range 0.00Hz~25.00Hz.
(3) When A48=-100%, A49=+100%, S00 Set Fre.range -50.00Hz~50.00Hz.
Note: When the motor is in -50.00~0Hz realise reverse, another setting
F45 Ten bit motor forward inverseas1 Command priority: Analog given positive and negative
values, on the F45 details refer to F45 Parameter Description
Description
Inverter output maximum frequency allowed
Setting range: 10.00~320.00Hz.
Keyboard potentiometer setting the start value.
Setting range: 0~100%.
Keyboard potentiometer setting the end value.
Setting range: 0~100%.
Display the value of potentiometer setting,
range: A45~A46.
Also can set diretly, Setting range: A45~A46.
Keyboard potentiometer setting the starting point
for the corresponding value.
Setting range: -100%~+100%.
Keyboard potentiometer settings corresponding
to the value of the end.
Setting range: -100%~+100%.
Displays the current size of the set
frequency,through the potentiometer setting.
Setting range: F12*A48~ F12*A49.
14