Section V Parameter Function Table
output frequency
FDT1=35Hz
FDT2=30Hz
FDT frequency
setting 1 arrived
FDT frequency
setting 2 arrived
FDT frequency
inspection level
ON means signal will react, OFF means signal will not react
When the choice of output signal(o21~o24)is set as14, inverter output frequency arrives at
or surpass FDT set frequency 1, the corresponding signal output terminal will react; When
inverter output frequency is below of frequency 1 FDT set, the corresponding signal output
terminal will not react.
When the output signal options(o21~o24)is set as 15, inverter output frequency reaches or
surpass FDT set frequency 2, the corresponding signal output terminal will react;When inverter
output frequency is below of frequency 3 FDT set, the corresponding signal output terminal will
not react.
When the output signal options (o21~o24)is set as16, inverter will firstly inspect FDT set
freuqnecy 1, then inverter output frequency arrives at or surpass FDT set frequency 1, the
corresponding signal output terminal will react;After terminal reaction, inverter will inspect FDT
set frequency 2, When inverter output frequency is below of frequency 2 FDT set, the
corresponding signal output terminal will not react.
o31 frequency inspection range
This parameter is used to define inspection range. When the difference of actual frequency
and inspected frequency has surpassed inspection range, terminal will output react.
e.g.: FDT set frequency 1 as 35Hz, FDT set frequency 2 as 30Hz.
Arrival of current upper
o32
limitation
Arrival of current lower
o33
limitation
o34
Current inspection range
When the output signal options (o21~o24)is set as 30, and inverter output current reach or
surpass "o32+o34", the corresponding output signal terminal will react. When the inverter output
current is less than o32-o34, The corresponding output signal terminal will not react.
When the output signal options (o21~o24)is set as 31, and inverter output frequency reach or
less than o33-o34, the corresponding output signal terminal will react;When the inverter output
current is more than o33+o34, The corresponding output signal terminal will not react.
o34 is used to define current inspection range. When the difference of actual current and
inspected current has surpassed inspection range, The output terminal will react.
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
o33~200%
o34~o32
0~o33
time
time
time
time
88
%
120
Y
%
20
Y
%
3
Y