2. PGM AND SIREN PROGRAMMABLE OUTPUTS
ADDRESS 21
PGM1 PROGRAMMABLE OUTPUT
In this address the events which will force the programmable output to move
into an active level are programmed.
A free combination of events activating the programmable output is allowed.
The output is activated whenever a programmed event occurs (function logical
OR) and is restored when all the programmed events are restored (function
logical AND).
Press the digit number corresponding to the desired parameter. If the LED with
the same number lights the parameter is set.
To switch between the first and the second group of parameters use the arrow
keys.
PGM1 PROGRAMMABLE OUTPUT - FIRST GROUP OF
PARAMETERS
Activated when an intervention into ALARM or ENTRY/EXIT zones under
1 ALARM
Security Mode occurs. The output is restored by entering a valid user code or
automatically after 1 min.
Activated when a PANIC type zone or the PANIC keys combination are
3 PANIC
activated. The output is restored by entering a valid user code.
Activated when the tamper of a zone or a TAMPER type zone are activated
3 TAMPER
regardless the status of the system - armed or disarmed. The output is restored
when the tamper is restored.
Activated when a FIRE type zone is activated. The output is restored by entering
4 FIRE
a valid code.
Activated for 4 seconds after entering a valid code.
5 FIRE RST
Activated when the system is armed. The output is restored when the system is
6 ÎN/OFF
disarmed.
PGM1 PROGRAMMABLE OUTPUT - SECOND GROUP OF
PARAMETERS
Activated when a MEDICAL type zone is activated. The output is restored by
1 MEDICAL
entering a valid user code.
Activated when the system is armed with a bypassed alarm or ENTRY/EXIT
2 PS/Bypass
zone or a Partial Security Mode (PARTSET) is on. The output is restored when
the system is disarmed.
Activated when the 220 V AC is lost. The output is restored when the AC
3 AC LOSS
power is restored.
Activated when the battery power is less than 11 V. The output is restored
4 BAT LOW
when the battery power is restored.
Activated when any of the fuses of the panel is blown. The output is restored
5 FUSE
when the fuse is replaced.
This attribute chooses the output active level. When the "-" is chosen (the LED
6 POL +/-
does not light) the active level is 0 V. When the "+" is chosen the output active
level is 12 V.
DEFAULT : ON/OFF, POL "+"