Save Configuration Menu; Restore Defaults Menu; Software Revision; Network - Teletek electronics REPEATER Installation And Programming Manual

Intelligent interactive fire alarm control panel
Table of Contents

Advertisement

Repeater – Installation and Programming Manual

7.3. Save Configuration Menu

Attention: Saving the system configuration is available only from access level 3!
In this menu the installer performs saving of the new found devices in the system configuration. The panel
will ask for confirmation of the action. The screen displays.

7.4. Restore Defaults Menu

Attention: The restore defaults menu is available only from access level 3!
In this menu the installer performs reset to default settings of the system configuration. The panel will ask for
confirmation of the action. The screen displays:
escape

7.5. Software Revision

In this menu the installer can review the software versions of the main board and used loop modules and
also has possibility for firmware update of the main processor unit. The screen displays:
Repeater Mainboard Ver. XX

7.6. Network

(supported for Soft. Version 2.8 and higher)
In this menu the installer can make the settings for the redundant network between fire panels.

7.6.1 Network Settings

To access the NETWORK settings, enter in the installer's menu - 3. NETWORK – 3.1) SETTINGS. The
screen displays:
3.1) SETTINGS
3.2) PANELS
3.3) AJAXLAN/GPRS
In this submenu the installer enters a number, name and sets the status of the panel in the redundant
network. Use the up/ down arrow buttons to set the panel number. Move on the second row with right arrow
button and enter a specific name up to 40 symbols, including intervals.
(1) – REDUNDANCY - Use the button to set an option for ignoring a fault message for broken connection in
the redundant network. Set OFF if you do not want to monitor the status of the connection in the redundant
network; set ON if you want to monitor the continuity of the redundant network.
(4) – CHANGE - Use the button to set the status of the panel in the redundant network - ENABLED (the
panel is enabled for operation in the network) / DISABLED (the panel is disabled for operation in the
network). When the panel is DISABLED from the network it will not receive messages from other panels and
will be visualized as FAULT.
Confirm the setting with 'ENTER' button. You can also escape from this menu with 'CANCEL' button.
Use the functional buttons to confirm or reject
the save configuration. You can also escape
from this menu with 'CANCEL' button.
Use the functional buttons to confirm or reject
the restore default settings. You can also
from this menu with 'CANCEL' button.