TeleTek

6. COMMUNICATOR PARAMETERS

Before configuring the communicator call your Monitoring company and specify
the necessary parameters - phone numbers, the subscriber account number,
communication report and event codes.
Before starting to configure the parameters erase the non-transmitted codes
from the event buffer in address 93 by pressing the 0 key once.
ADDRESS 60
PRIMARY PHONE NUMBER (PHONE 1)
In this address the primary phone number for communication with the monitoring
Tel No 1
station is set. Hexadecimal indication. The maximum lenght of the phone number
is 16 symbols, including the pause symbols (ON and 2) and the symbols for
entering a DTMF dialing (ON and 1).
DEFAULT : No phone number entered
ADDRESS 61
SUBSCRIBER ACCOUNT NUMBER 1
This is the panel ID number for the primary monitoring station. The lenght of
PANEL ID 1
the number is 3 or 4 digits (depending on the report format - 3x or 4x). The 0
symbol is replaced by an A (See the hexadecimal programming table in Appendix
A).
DEFAULT : 9999
ADDRESS 62
COMMUNICATION REPORT 1
COMMUNICATION The communication report types to the monitoring station are listed in the table
REPORT 1
DEFAULT : 1
ADDRESS 63
REPORT FORMAT 1
Choosing the format of the set report 3x1, 4x1. The LEDs from 1 to 6 light.
x1
Choosing the format of the set report 3x2, 4x2. The LEDs from 1 to 6 do not
x2
light.
DEFAULT : x2
ADDRESS 64
SECONDARY PHONE NUMBER (PHONE 2)
In this address the secondary phone number for communication with the
Tel No 2
monitoring station is set. Hexadecimal indication. The maximum lenght of the
phone number is 16 symbols, including the pause symbols (ON and 2) and the
symbols for entering a DTMF dialing (ON and 1).
DEFAULT : No entered phone number
CA60Plus
below. The symbols from 0 to B could be used.
[0]
User report - dialer
[1]
SP=10 pps; HS=KO=1400Hz; Data=1900Hz; 3x1, 3x2, 4x1, 4x2;
[2]
SP=10 pps; HS=KO=1400Hz; Data=1900Hz; EXT; 3x1, 4x1;
[3]
SP=20 pps; HS=KO=1400Hz; Data=1900Hz; 3x1, 3x2, 4x1, 4x2;
[4]
SP=20 pps; HS=KO=1400Hz; Data=1900Hz; EXT; 3x1, 4x1;
[5]
SP=20 pps; HS=KO=2300Hz; Data=1800Hz; 3x1, 3x2, 4x1, 4x2;
[6]
SP=20 pps; HS=KO=2300Hz; Data=1800Hz; EXT; 3x1, 4x1;
[7]
SP=40 pps; HS=KO=2300Hz; Data=1800Hz; 3x1, 4x2;
[8]
SP=40 pps; HS=KO=2300Hz; Data=1800Hz; EXT; 3x1;
[9]
SP=40 pps; HS=KO=2300Hz; Data=1800Hz; 3x1, 4x2; Checksum;
[A]
SP=40 pps; HS=KO=2300Hz; Data=1800Hz; EXT; 3x1; Checksum;
[B]
ADEMCO CONTACT ID
[C]...[F] - reserved for future use
23
Installation Manual