SIMPO Addressable Fire Alarm Panel – Maintenance Menus

3.3.2 Disabling Devices

Every loop device can be disabled, as the panel will not follow the operation of the disabled device and will not respond
to fire or fault messages from it. The LED 'Disable' on the front panel is lighting on.
The panel will ask if you want to disable the selected device only (button (2) THIS) or all present devices (button (3) ALL)
at the respective Loop number. The exit is automatic to the main screen DEVICES SETUP, as the disabled devices are
displayed with status DISABLED.
For example, if the selected device is connected to Loop 1, when pressing the button (3) ALL, all present devices
connected to Loop 1 will be disabled in the system configuration. To disable in the system configuration all present
devices connected to Loop 2, the installer has to select a device in Loop 2 and press button (3) ALL. Quick switching
between Loop 1 and Loop 2 can be performed with button (1) GO TO.
To enable the device again, select its address and press the active button (4) ENABLE.
Note: If at the moment of enabling the device, it is in fire alarm mode (the fire signal was generated earlier, when the
device was still disabled) the panel will alert for the fire alarm situation immediately!

3.4. Panel Outputs Menus

This menu allows the technician to disable/ enable and to set time delay for some of the outputs of the control panel:
- Sounder Outputs (SND 1, SND 2)
- Extinguish Output (EXT)
- Fire Output (FIRE)
- Fault Output (FAULT)
To access outputs parameters, enter in the menu - 5. PANEL OUTPUTS. The submenus are allocated in two screens.

3.4.1 Sounders Outputs

In this submenu the technician can disable/ enable the sounders activation and the time delay operation.
To access the SOUNDER submenu, enter in menu - 5. PANEL OUTPUTS - SOUNDER (1).
• ON - The delay of sounder outputs will be active when DAY operation mode is set.
• OFF - No delay of sounder outputs activation. The sounder outputs are activated immediately.
• SCHEDULE - The delay of sounder outputs will be active on schedule.
All set parameters are confirmed with ENTER button.
The functional buttons have the following action:
(2) - Press to change the status of the sounder outputs. Every pressing
of the button changes alternatively the ENABLED - DISABLED status.
When the sounder outputs are disabled the LEDs 'Sounder Output
Fault/ Disable' and 'Disable' light on permanently.
(4) - Press to set the time delay operation. Every pressing of the button
changes the 'Delay' setting: