Teletek electronics CA60Plus Installation Manual page 18

Security control panel
Hide thumbs Also See for CA60Plus:
Table of Contents

Advertisement

TeleTek
ADDRESS 22
PGM2 PROGRAMMABLE OUTPUT
DEFAULT : ALARM, TAMPER, POL "+"
ADDRESS 23
PGM3 PROGRAMMABLE OUTPUT
DEFAULT : AC LOSS, BAT LOW, FUSE, POL "+"
ADDRESS 24
SIREN PROGRAMMABLE OUTPUT
ALARM
TAMPER
PANIC
FIRE
DEFAULT : ALARM, PANIC, TAMPER, FIRE/ALW
CA60Plus
Programming as in address 21.
Programming as in address 21.
The SIREN output is activated by 4 events. The active level of this output is low
(0 V) and could not be programmed.
A free combination of events activating this output is allowed. The output is
restored after the bell time - programmed in address 32 - is expired.
Activated when an intervention into ALARM or ENTRY/EXIT zones under
Security Mode occurs. The output is restored by entering a valid user or master
code or automatically after the bell time is expired.
Activated when the tamper of a zone or a TAMPER type zone are activated
regardless the status of the system - armed or disarmed. In case the event is not
chosen to activate the SIREN output, it will cause an audible signal from the
keypads. The output is restored by entering a valid user or master code or
automatically after the bell time is expired.
Activated when a PANIC type zone or the PANIC keys combination is
activated. The output is restored by entering a valid user or master code.
Activated when a FIRE type zone is activated. The output is restored by entering
a valid code. This event ALWAYS activates the SIREN output and could
not be cancelled.
18
Installation Manual